177

Network Communication Chapter 2

2. In the Controller Properties dialog box, from the System Protocol tab,

choose the settings for the controller, then choose OK.

System Protocol

Field

DF-1 Master Protocol

DF-1 Slave Protocol

DF-1 Radio Modem Protocol

Station Address

Controller station address number

Controller station address number

Controller station address number

Transmit Retries

3

3

N/A

ACK Timeout

50

N/A

N/A

Slave Poll Timeout

N/A

3000

N/A

Reply Message Wait

5

N/A

N/A

Polling Mode

Message: polls the slave by using
the Message instruction

Slave: initiates messages for
slave-to-slave broadcast.

Standard: schedules polling for the
slave.

N/A

N/A

EOT Suppression

N/A

Disable

N/A