Chapter 5 Add a PowerFlex 40 Drive
to make the following parameter value edits on your PowerFlex
40 drive.
1. If your PowerFlex 40 drive has been previously used, reset it to factory defaults.
a. Change the value of parameter P041 from 0 to 1.
The drive is reset and fault F048 is displayed and blinks.
b. Press
to clear the fault.
c. Press
to return to editing parameters.
2. Change the value of parameters P036 and P038 from 0 to 5.
Changing these parameters switches control the Start Source and the Speed Reference
from the keypad to the communication port. This enables you to control these functions
by using RSLogix 5000 tags.
3. Press
to accept parameter edits.
4. Press
to return to the speed display.