Chapter 3 Embedded I/O

Digital Outputs

Each of the 1769-L23 and 1769-L23E packaged controllers provides 16
solid-state DC outputs. This section describes how to wire and configure the
OB16 DC outputs.

DC Output Wiring

Basic wiring

(1)

of for the embedded OB16 Discrete Outputs (sourcing

outputs)

(2)

is shown below.

(1)

Recommended Surge Suppression - Use a 1N4004 diode reverse-wired across the load for transistor outputs
switching 24V DC inductive loads. For additional details, refer to Industrial Automation Wiring and Grounding
Guidelines, Allen-Bradley publication

1770-4.1

.

ATTENTION

Miswiring the outputs to an AC power source or applying
reverse polarity causes damage to the outputs.

Be careful when stripping wires. Wire fragments that fall into a
wiring terminal could cause damage at powerup. Once wiring is
complete, make sure the terminal is free of all metal fragments.

(2)

Sourcing Output - Source describes the current flow between the I/O and the field device. Sourcing output
circuits supply (source) current to sinking field devices. Field devices connected to the negative side (DC
Common) of the field power supply are sinking field devices. Field devices connected to the positive side (+V) of
the field supply are sourcing field devices. Europe: DC sinking input and sourcing output circuits are the
commonly used options.

+DC

24V DC

(source)

-DC

DC COM

OUT 14

OUT 12

OUT 10

OUT 8

OUT 6

OUT 4

OUT 2

OUT 0

OUT 15

OUT 13

OUT 11

OUT 9

OUT 7

OUT 5

OUT 3

OUT 1

+VDC

CR

CR

CR

CR

CR

CR

CR

CR

CR