Add the 1769-SDN Module to the RSLogix 5000 Project

3. In the Name box, type a

name for your SDN module.

4. In the Slot box, type or

choose the Slot number.

The slot number you specify
depends on which 1769-L23
controller you use.

5. In the Input Size and Output Size boxes, type or choose values to accommodate the

input and output sizes of the modules in your system.

This example uses 20.

For more information about determining input and output sizes, see the DeviceNet
Modules in Logix5000 Control Systems User Manual, publication

DNET-UM004

.

6. From the Electronic Keying pull-down, choose Compatible Keying.

7. Check the Open Module Properties check box and click OK.

1. In the RSLogix 5000 configuration

tree, right-click CompactBus
Local
and select New Module.

2. Under Communications,

select 1769-SDN with the
series letter recorded on the

Network Worksheet

and click

OK.