Chapter 3 Embedded I/O
9. Enter the counter’s maximum and minimum counts.
The highest maximum count you can use is +2147483647. The lowest
minimum count limit you can use is -2147483648.
10. Specify the counter mode you need for your application.
11. Use the Operational Mode pull-down menu to select the counter’s
operational mode.
Use this counter mode
When your application requires this behavior
Ring Counter
If the current count value is counting up and exceeds the
maximum count, the counter begins counting again from the
minimum count.
If the current count value is counting down and exceeds the
minimum count, the counter begins counting again from the
maximum count.
Linear Counter
If the current count value is over or under the maximum and
minimum counts specified, counting stops and
overflow/underflow bits are set.
TIP
The operational modes that are available depend upon the
number of HSC counters you are using.
Use this table as a reference when determining what operation
modes you can use in your application.
Number of
Counters
Counter
Operational Mode
Gate or Preset
Functionality
1
0
Any
All
1…3
Not available
2
0
Any
All
1
Any
All
2 and 3
Not available