5.3 Module/Unit Connections

KV

-300

KV-10/80

5

Chapter 5 KV-300 Hardware

1-178

Upright

Back

Side

30 mm

30 mm

30

mm

a

a

b

Power

supply

5.3

Module/Unit Connections

5.3.1

Environmental Requirements

Choose an appropriate location for installing the KV Series modules.

■ Avoid the following:
•

Exposure to direct sunlight.

•

Exposure to temperatures below 0°C (32°F) or exceeding 50°C (122°F).

•

Exposure to humidity below 35%RH or exceeding 85%RH.

•

Areas where condensation occurs due to sudden drops in temperature.

•

Exposure to corrosive or flammable gases.

•

Exposure to airborne dust, metal particles, oil, or corrosive substances such as
salt.

•

Exposure to strong vibration or impact.

•

Locations where water, oil, or chemicals may splash the product.

•

Exposure to strong magnetic or electrical fields.

Use only the specified cable when connecting to terminal modules. Use of any
other cable may cause communication errors.

5.3.2

Installation Guidelines

•

Install the CPU upright, as shown.

•

Do not install the CPU on its back or side.

•

Maintain a 30 mm gap above and below the module so that a finger can be
inserted to release the lock lever and remove the module.

•

Maintain a 30 mm gap between the module
and adjacent equipment to avoid
interference from the power supply.

CAUTION