Appendix B Specifications and Dimensions

KV-300 Series

Appendicies

Appendices

1-396

For KV-10/80 users

Output specifications

Relay service life: Mechanical: 20 million operations min.

Electrical: 100 thousand operations min. (20 times/min)

I/O circuit configuration

■ Input circuit (relays 0000 to 0005)

•

*4.3 kΩ used only for terminals connected to relays other than 0000 through
0005.

•

Input from both NPN [(+) connected to COM] and PNP [(–) connected to COM]
type transistors are applicable.

■ Output circuit (relay contact)

•

Applicable only to the KV-40R, KV-24R, KV-16R, KV-10R, and KV-8ER.

•

A separate power supply is required for the load.

Type of output

Relay

BJT

MOS-FET

Rated load

250 VAC/

30 VDC 0.3 A

30 VDC 0.25 A

Max. voltage at OFF

—

30 VDC

30 VDC

Leak current at OFF

—

100 µA max.

5 µA max.

Residual voltage at

—

1V

—

ON

Resistance at ON

50 mΩ max.

—

1Ω max.

OFF

→ON 10 ms max.

50 µs max.

350 µs max.

(terminals 500 on

(terminals 500 and 501)

KV-80T(W): 3 µs max.)

2 ms max.
(other terminals)

ON

→OFF 10 ms max.

450 µs max.

150 µs max.

(terminals 500 on
KV-80T(W): 20 µs)

Photocoupler insulation

IN

COM

*4.3k

+

+

Internal circuit

Ω

510 Ω

24 VDC

3k Ω

Power supply for operating
relay 24-VDC power is
internally supplied.

COM

+

+

Internal circuit

L

~

OUT

Switching
time

KVHKA Appendix.p65

08.3.11, 11:05 AM

396