Kv -300 – KEYENCE Visual KV Series User Manual

Page 364

Advertising
background image

9.2 Configuration

KV-10/80 Series Only

KV

-300

KV-10/80

Chapter 9 KV-AD4/DA4 Analog I/O Unit

1-340

9

Analog output terminal assignment

Terminal

Signal

Description

• Output range: -10 to +10 V

NC (No connection)

Analog voltage output ch0

Analog voltage output ch1

Analog voltage output ch2

Analog voltage output ch3

Analog current output ch0

Analog current output ch2

Analog current output ch1

Analog current output ch3

I0

I1

I2

I3

C0

C1

C2

C3

C4

C5

C6

C7

V0

V1

V2

V3

• Output range: 4 to +20 mA

Ground for analog signal (connected internally)

Note 1: Separate terminals are used for analog voltage input and analog current
output. Take care not to miswire these terminals.

Note 2: Do not connect the output voltage and output current to terminals of the
same No., for example, by connecting external instruments to both V0 and I0.
Doing so might cause the KV-DA4 to malfunction.

Dimensions

C0

C1

C2

C3

C4

C5

C6

C7

V0

V1

V2

V3

I0

I1

I2

I3

ANALOG OUT

KEYENCE
KV - DA4

POWER

2-ø5 (mounting hole)

99

31

65

39

43

35.4

90

111

KVHKA Chap 09.p65

08.3.11, 11:20 AM

340