Chapter 1 Configuration and Specifications

1-15

1

1

Visual KV

Series

1.4.4

Relationship between Continuous Simultaneous ON
Ratio and Ambient Temperature

If the number of I/O points which turn ON at the same time exceeds the
specifications range, the unit may be damaged.

The graphs below show the relationship between the ambient temperature and
the continuous simultaneous ON ratio.

Load current L:

CAUTION

110

100

90

80

70

60

50

40

30

20

10

0

30 35 40 45 50

39

(102.2)

41

(105.8)

42

(107.6)

46 (114.8)

44 (111.2)

63%

38%

25%

49

(120.2)

L=0

L=1/2Max.

L=1/2Max.

L=Max.

L=Max.

L=0

(86)

(95)

(104)

(113) (122)

110

100

90

80

70

60

50

40

30

20

10

0

86%
79%

64%

L=Max.

L=0,1/2Max.

L=Max.

47 48

(116.0)(118.4)

45 (113)

30 35 40 45 50

(86)

(95)

(104)

(113) (122)

110

100

90

80

70

60

50

40

30

20

10

0

(105.8)(109.4)(114.8)(116.6)

41

43

46

47

86%

68%
60%

30%

L=0

L=Max.

L=0

L=1/2Max.

30 35 40 45 50

(86)

(95)

(104)

(113) (122)

110

100

90

80

70

60

50

40

30

20

10

0

30 35 40 45 50

(86)

(95)

(104)

(113) (122)

110

100

90

80

70

60

50

40

30

20

10

0

45 (113)

58%

30 35 40 45 50

(86)

(95)

(104)

(113) (122)

110

100

90

80

70

60

50

40

30

20

10

0

48 (118.4)

80%

30 35 40 45 50

(86)

(95)

(104)

(113) (122)

110

100

90

80

70

60

50

40

30

20

10

0

49 (120.2)

88%

30 35 40 45 50

(86)

(95)

(104)

(113) (122)

110

100

90

80

70

60

50

40

30

20

10

0

30 35 40 45 50

(86)

(95)

(104)

(113) (122)

Derating when KV-10AR is mounted upward

Individual unit
With expansion unit

Individual unit
With expansion unit

Individual unit
With expansion unit

Individual unit
With expansion unit

Individual unit
With expansion unit

Individual unit
With expansion unit

Individual unit
With expansion unit

Individual unit
With expansion unit

Derating when KV-10AR is mounted in front

Continuous simultaneous

ON

ratio

(%)

Ambient temperature [°C]
[°F] for figure in ( ).

Continuous simultaneous

ON

ratio

(%)

Ambient temperature [°C]
[°F] for figure in ( ).

Derating when KV-10AT(P) is mounted upward

Derating when KV-10AT(P) is mounted in front

Continuous simultaneous

ON

ratio

(%)

Continuous simultaneous

ON

ratio

(%)

Ambient temperature [°C]
[°F] for figure in ( ).

Derating when KV-10DR is mounted upward

Derating when KV-10DR is mounted in front

Continuous simultaneous

ON

ratio

(%)

Ambient temperature [°C]
[°F] for figure in ( ).

Continuous simultaneous

ON

ratio

(%)

Ambient temperature [°C]
[°F] for figure in ( ).

Derating when KV-10DT(P) is mounted upward

Derating when KV-10DT(P) is mounted in front

Continuous simultaneous

ON

ratio

(%)

Ambient temperature [°C]
[°F] for figure in ( ).

Continuous simultaneous

ON

ratio

(%)

Ambient temperature [°C]
[°F] for figure in ( ).

1.4 KV-10AR/AT(P)/DR/DT(P) (10-I/O Basic Unit)

(AC power output
capacity at 400 mA)

(Individual current consumption
when KV-D20 is connected)

(Service power
output current)

(Expansion
unit current
consumption)

=

+

Ambient temperature [°C]
[°F] for figure in ( ).