7.7 Non-procedure Mode Programming

KV-300 Series Only

KV

-300

KV-10/80

Chapter 7 KV-L2 Serial Interface Module

1-296

7

5. First relay no. +4

Turns ON when a break signal of approximately 160 msec is transmitted. Automati-
cally turns OFF after transmission is completed. Transmission is enabled while the
first relay no. +3 is OFF.
Use the SET instruction or KEEP instruction to turn the relay ON/OFF.

Assigning data memory addresses

200 DM addresses, including the first DM no., are assigned.
The assigned DM addresses have the following functions.

Number of data bytes
The number of bytes in the first DM no. +0 and the first DM no. +100 becomes a
binary value. Write the binary data using the LDA/STA instruction or DW instruction.

Text data
Enter the text data in ASCII, by byte per DM. ("00" is entered in the 8 high-order bits
and ASCII code is entered in the 8 low-order bits.)
Write the text data using the LDA/STA instruction or DW instruction.

DM No.

Assigned data

First DM No. +0

Number of bytes of text data loaded

+1 to +99

Text data to be received

+100

Number of bytes of text data to be received

+101 to +199

Text data to be transmitted