7.5 KV Mode Programming

KV-300 Series Only

KV

-300

KV-10/80

Chapter 7 KV-L2 Serial Interface Module

1-261

1

7

E2

Program
unregis-
tered

• "M1" was transmitted with no

program stored in the KV-300
CPU.

• Reading of timer/counter was

attempted.

• Register a program into the

KV-300 CPU.

• Check the program for the

timer/counter number being
used and specify it.

E3

CPU fault

• Hardware error was detected

in a KV-300 CPU.

• Turn the power to the KV-300

OFF and then ON again. If
the cause of the error is not
corrected, the CPU may be
faulty. Contact your nearest
KEYENCE office.

E4

Write-
protected

• Attempt was made to change

the preset value of a counter,
timer, or CTC in a write-
protected program.

• Write-enable the program,

and change the preset value.

E5

CPU error

• "M1" was transmitted before

an error message was
cleared from the KV-300.

• Clear the error message from

the KV-300 CPU, and remove
the cause of the error.

Error code list

Error codes included in responses to the KV-300 CPU error check command (?E)
as well as error descriptions, causes of error, and remedies are listed below.

Error

Code

Description Cause

Remedy

00

No error

10

CALL nest
error

• Subroutines are nested to four

levels or more.

• These errors may occur when

a program is executed. Check
the program while paying
particular attention to usage of
subroutines and the INT
instruction, and restore the
program accordingly.

11

FOR nest
erro

• FOR-NEXT instructions are

nested to eight levels or more.

12

INT nest
error

• Five levels or more of inter-

rupts occurred simultaneously.

13

MPS nest
error

• MPS/MPP instructions are

nested to eight levels or more.

20

Memory
erased

• Contents of RAM are erased.

All data in data memory and
current values of counters in
the KV-300 CPU are cleared.

• Check data in data memory

and current values of counters,
and re-enter correct data. The
KV-300 CPU returns to normal
operation after the error is
cleared.

30

Scan time
error

• Scan time exceeds 300 ms.

• Check the program again.

• Be sure that there is no

excessive repetition using the
FOR-NEXT loop.

• Be sure that an interrupt is not

executed at a higher rate.

40

NO PRO-
GRAM

• An attempt was made to

operate the KV-300 CPU with
no program stored.

• Write a program into the

KV-300 CPU.

50

SND/RTN
failure

• Hardware error was detected

in a KV-300 CPU.

• Turn the power to the KV-300

OFF and then ON again. If
the cause of the error is not
removed, the KV-300 CPU
may be faulty. Contact
nearest KEYENCE office.

51

Division by
zero

52

Address
error

53

Invalid
instruction

54

Watchdog
timer error