4 calculating output data (d/a) – KEYENCE Visual KV Series User Manual

Page 347

Advertising
background image

8.4 Programming

KV-300 Series Only

KV

-300

KV-10/80

Chapter 8 KV-AN6 Analog I/O Module

1-323

1

8

8.4.4

Calculating Output Data (D/A)

To output analog data, write the data into the analog output data memory ad-
dresses.
Calculate the numerical value to be written into data memory.

Voltage output

DM value = Output voltage/Output range resolution x 16

Current output

DM value = (Output current -12 [mA])/0.004 [mA] x 16
To convert a 16-bit DM value to an effective 12-bit value, multiply the 16-bit value
by 16.

Example 1

When +7.5 V is output in the ±10 V range
7.5 V/5 mV x 16 = 24000
The DM value is 24000.

Example 2

When -5 V is output in the ±5 V range
5 V/2.5 mV x 16 = 32000
Since the output voltage in this example is negative, set the result by subtracting
32000 from 0 as the DM value.

Example 3

When 18 mA is output in the 4-to-20 mA range
(18 mA - 12 mA)/0.004 x 16 = 24000
The DM value is 24000.

KVHKA Chap 08.p65

08.3.11, 11:19 AM

323