7.6 Display Interface Mode Programming

KV-300 Series Only

KV

-300

KV-10/80

Chapter 7 KV-L2 Serial Interface Module

1-271

1

7

Note 1: Turn off the power switches before setting switches.

Note 2: Communications protocols for the modules to be connected must be identi-
cal; otherwise, communication will fail. For settings of external units to be connected,
refer to the operation manuals supplied with the respective units.

Note 3: For settings of the display device, refer to the User’s Manual of your display
device.

Note 4: The communications protocols settings apply to both ports 1 and 2. The two
ports cannot be set to different protocols.

Communications control procedure

In Display Interface mode, the KV-L2 provides a special interactive communications
procedure, detailed below.

Communications procedure

In Display Interface mode, the host computer sends a command to the KV-L2 and
the KV-L2 automatically returns a response.

FCS (frame check sequence)

The FCS is a method of detecting communications errors. An 8-bit exclusive OR
from the top of the command or response up to the last character of the text is
converted into a 2-character ASCII code.

Calculation example

@ 0

1

W D

0

3

E

8

1

9

6

4

2

6

*

CR

station no. header code---------------------------text---------------------------FCS terminator

@ 0

1

0

0

0

0

0

0

Exclusive OR

0

0

0

1

1

0

0

0

0

Exclusive OR

1

0

0

1

1

0

0

0

1

Exclusive OR

1

0

0

1

1

0

0

0

1

:

:

:

:

6

0

0

1

1

0

1

1

0

Exclusive OR

4

0

0

1

1

0

1

0

0

Exclusive OR

---------------------------------------------------------

0

0

1

0

0

1

1

0

ASCII

2

6

<----------FCS Value

(Host computer)

Station no.

Header code

Text

FCS

Terminator

Command

KV-L2

Station no.

Header code

Text

FCS

Terminator

Response