9.5 Programming Examples

KV-10/80 Series Only

KV

-300

KV-10/80

Chapter 9 KV-AD4/DA4 Analog I/O Unit

1-363

1

9

Example 2: Outputting Analog Current (4 to 20 mA)

•

Data that has been written to DM0000 is converted to digital data for analog
output.

•

The digital data is sent to analog output I0 on the KV-DA4.
(Digital data is written to data memory DM0996.)

•

4 mA is output when input 0000 is ON.

•

20 mA is output when input 0000 is OFF.

1. #4000 is written to DM0000 when input 0000 is ON.
2. #20000 is written to DM0000 when input 0000 is OFF.
3. ((DM0000

÷

4

µA)

-

1000) is calculated, and the calculation result is written to

DM0001.

4. Before the digital data is written to data memory for D/A conversion, check that

the data is #4095 or less.

Note: An unsteady value will be output if a value outside the range 0 to 4095 is
written to data memory for D/A conversion.

5. The output data will be updated at the rising edge of special utility relay 2800. (As

internal relay 1000 switches ON/OFF at each scan, the output data will be
updated every two scans.)

Note: In the case of current output, DM0996 need not be initialized (#2000 written to
DM0996) when the power is turned ON.

0000 #04000

DW

0000

DM0000

#20000

DM0000

DW

2002 DM0000

LDA

#00004

DIV

DM0001

STA

#01000

SUB

1000

1000

1000

2800

2002

2011

DM0001

LDA

#04095

CMP

DM0001

LDA

DM0996

STA

1

2

3

4

5

( )

( )