7.2 Configuration

KV-300 Series Only

KV

-300

KV-10/80

Chapter 7 KV-L2 Serial Interface Module

1-242

7

7.2.2

System Configuration

The following examples show KV-L2 system configurations in 1:1 and 1:n connec-
tion patterns. These examples also highlight the functional differences between
these connection patterns.

Connection to the KV-300 CPU

A maximum of two KV-L2s can be connected to the KV-300 CPU. The KV-L2s
should be installed at the right end of a system.

1:1 connection

Connect the KV-L2 to an external unit (such as a personal computer) through the
RS-232C or RS-422A ports.

Note: Use RS-232C communications for connections of up to 15 meters; use RS-
422A communications for connections of up to 500 meters.

1:n connection

Up to 10 KV-L2 modules can be connected to an external unit (such as a personal
computer) through the RS-422A port.

KV-U4

KV-300

KV-L2

KV-L2