3. Command data

Set the relay no., data memory address, and instruction word using ASCII char-
acters. For reference, the relay no. "0015" is converted to "30 30 31 35" in ASCII
code values, and the instruction word "CNT_" to read the set value of counter/
timer (R#) is converted to "43 4E 54 20" in ASCII codes .

Command code(ASCII characters)
ASCII code conversion for FCS calculations

4. FCS (frame check sequence)

The FCS (frame check sequence) is a method for detecting a communication
error. It calculates the exclusive OR within the following range. The calculated 8-
bit data is converted to a 2-ASCII character.

Description of commands and responses

This section describes the format of commands and responses. In the following
figure, "n" represents one ASCII character (1 byte). The characters stand for two
types of values: One is a decimal value representing a numeric value between 0 and
9 for station no., channel no., address no., and timer/ counter values: the other is a
hexadecimal value representing a numeric value between $0 and $F for binary data
bit information of I/O or Data Memory.

Read I/O relay/internal utility relay (RR)

This command reads the I/O relays/internal utility relays starting from the specified
channel no. within the specified range.

Command format

Response format (When the command is executed normally, the response

includes the end code "00".)

Read temporary data memory address/analog timer (RH)

This command reads the current value of the temporary data memory address/
analog timer starting from the specified no. within the specified range.

@

C

R

FCS

Station no.

Header

code

Command/response

data

FCS calculation range

Station no.

nn

@

RR

FCS

C

R

End code

nn

Data
nnnn

Data
nnnn

Header code

Terminator

Data of read start ch.
+1(in hexadecimal)

Data of read start ch.
(in hexadecimal)

@

FCS

RR

C

R

Station no.

nn

Read start

ch.

nnnn

Number of

channels to

read: nnnn

Header

code

00 to 15

(in decimal)

Terminator

0001 to 0180

(in decimal)

0000 to 0179

(in decimal)

0 0 1 5

C N T

4EH

30H

31H

30H

35H

20H

43H

54H

KVHKA Chap 07_5to10.p65

08.3.11, 11:18 AM

277