Timer/counter setting change, Chg: t/c set-v) [fnc70 – KEYENCE Visual KV Series User Manual

Page 248

Advertising
background image

6.3 Functions

Chapter 6 Handheld Programmer

1-224

6

TIMER/COUNTER SETTING CHANGE

PROGRAM mode

(CHG: T/C SET-V) [FNC70]

RUN mode

Function

Changes preset value of timer/counter, or displays preset value for monitoring.
Result obtained when TIMER/COUNTER SETTING CHANGE is executed.

Mode of handheld

programmer

PROGRAM mode

Timer input: ON
Counter input: ON

*1

Specified value ≥ current value:
The preset value will be changed to
the specified value.
Specified value < current value:
The preset value will be changed to
the specified value.
The current value will also be
changed to the specified value.
When the current value is 0,
however, the contact output goes
ON.

Timer input: OFF
Counter input:
OFF

*2

The preset value
will be changed to
the specified value.
The current value
will also be
changed to the
specified value.
The contact output
goes OFF.

The preset value
will be changed to
the specified value.
The current value
will also be
changed to the
specified value.
The contact output
goes OFF.

The preset value
will be changed to
the specified value.
The current value
will also be
changed to the
specified value.
The contact output
goes OFF.

0.1-s timers (TMR)
0.01-s timers (TMH)
1-ms timers (TMS)

The preset value will be changed
to the specified value.
The contact output goes OFF.

Specified value ≥ current value:
The preset value will be changed
to the specified value.
Specified value < current value:
The preset value will be changed
to the specified value.
The current value will also be
changed to the specified value.
When the current value is equal
to the preset value, however, the
contact output goes ON.

Specified value ≥ current value:
The preset value will be changed
to the specified value.
Specified value < current value.
The preset value will be changed
to the specified value.
The current value will also be
changed to the specified value.
The contact output goes OFF.

The preset value will be changed to the specified value.
When the preset value of CTC0 or CTC2 is changed, the current value of CTH0 or CTH1 also
varies according to the specified value for CTC0 or CTC2.

When changing the preset value of CTC0:
(When special utility relay 2103 is ON:)
Specified value for CTC0 ≤ current value of CTH0:
The current value of CTH0 will be changed to "the specified value for CTC0 - 1".
Specified value for CTC0 > current value of CTH0:
The current value of CTH0 will not be changed.
(When special utility relay 2103 is OFF:)
The current value of CTH0 will not be changed. The contact of CTC0, CTC1, CTC2, or CTC3
does not change.

When changing the preset value of CTC2:
(When special utility relay 2203 is ON:)
Specified value for CTC2 ≤ current value of CTH1:
The current value of CTH1 will be changed to "the specified value for CTC2 - 1".
Specified value for CTC2 > current value of CTH1:
The current value of CTH1 will not be changed.
(When special utility relay 2203 is OFF:)
The current value of CTH1 will not be changed.

Counters (CTR)

Up-down
counters (UDC)

High-speed
counter
comparators
(CTH)

Type of timer/
counter

Specified value ≥ current value:
The preset value will be changed to
the specified value.
Specified value < current value:
The preset value will be changed to
the specified value.
The current value will also be
changed to the specified value.
When the current value is equal to
the preset value, however, the
contact output goes ON.

Specified value ≥ current value:
The preset value will be changed to
the specified value.
Specified value < current value.
The preset value will be changed to
the specified value.
The current value will also be
changed to the specified value.
The contact output goes OFF.

RUN mode

KVHKA Chap 06_3&4&5.p65

08.3.11, 11:17 AM

224