9.5 Programming Examples

KV-10/80 Series Only

KV

-300

KV-10/80

Chapter 9 KV-AD4/DA4 Analog I/O Unit

1-360

9

Example 1: Inputting Analog Voltage (-10 to +10 V)

The analog input data from analog input V0 on the KV-AD4 is calculated.
(The digital data of data memory DM0992 is used for this operation)

The calculated data is written to DM0000. (If the calculated value is a negative
value, 2’s complement is written.) Data is written in mV units.

For example:

When the input is +10V, "10000" (data x 1000) will be written to DM0000.
When the input is -10V, "-10000 (#55536)" (data x 1000) will be written to

DM0000.

1. The data of DM0992 will be calculated, and the calculation result (data x 5 mV -

10000) will be written to DM0000.

Note: "2007" (first scan OFF at power ON) must be set as the input condition. In the
case of analog input, an unsteady value will be input for the first scan when the
power is turned ON.

Example 2: Inputting Analog Current (4 to 20 mA)

The analog input data from analog input I0 on the KV-AD4 is calculated.
(The digital data of data memory DM0992 is used for this operation.)

The calculated data is written to DM0000. Data is written in µA units.

For example:

When the input is 4 mA, "4000" (data x 1000) will be written to DM0000.
When the input is 20 mA, "20000" (data x 1000) will be written to DM0000.

2007

DM0992

LDA

#00005

MUL

DM0000

STA

#10000

SUB

1

1. The data of DM0992 will be calculated, and the calculation result (data x 4 µA +

4000) will be written to DM0000.

Note: "2007" (first scan OFF at power ON) must be set as the input condition. In the
case of analog input, an unsteady value will be input for the first scan when the
power is turned ON.

2007

DM0992

LDA

#00004

MUL

DM0000

STA

#04000

ADD

1