7.3 Installation

KV-300 Series Only

KV

-300

KV-10/80

Chapter 7 KV-L2 Serial Interface Module

1-246

7

Setting the TERMINATOR (terminal resistor)

Turn off the power switch before setting the TERMINATOR switch.
When using the RS-422A communications mode, set the TERMINATOR selection
switches of the KV-L2s at both ends of the connection cable to ON.
Set the TERMINATOR selection switches of any KV-L2s connected between the
leftmost and rightmost KV-L2s to OFF. If set to ON, normal communications will not
take place.

Note: When setting port 2 to RS-232C mode, set the TERMINATOR selection
switch to OFF.

Setting the station no.

When the RS-422A communications mode has been selected, a station no. must be
assigned to each KV-L2 to establish which KV-L2 is to communicate with the
external unit (personal computer). Turn off the power switch before setting the
station no.

Note 1: When the KV-L2 is set to RS-422A communications mode, set the TERMI-
NATOR (terminal resistor) to ON.

Note 2: Set the terminators of the modules connected in intermediate positions
(between the leftmost and rightmost KV-L2s) to OFF.

Note 3: Do not assign the same station no. to more than one module; otherwise,
data communication will be disrupted.

Station no. setting dial

F

E

D

C

B

A

9 8 7

6

5

4

3

2

1

0

Set the station no. to a number within the range 0 to 9.
Do not assign the same station no. to more than one
KV-L2 module. The module is factory-set to 0.

TERMINATOR selection switch

ON

OFF

TERMINATOR

Termination required: Set the switch to
the left (ON) position.
No termination required: Set the switch
to the right (OFF) position.

*

*

In the figure above, only those KV-L2s marked with an
asterisk require their TERMINATOR switches set to ON.

KVHKA Chap 07_1to4.p65

08.3.11, 11:18 AM

246