9.4 Programming

KV-10/80 Series Only

KV

-300

KV-10/80

Chapter 9 KV-AD4/DA4 Analog I/O Unit

1-355

1

9

How to calculate digital data when outputting analog current

Digital data = (output current (

µ

A)

÷

resolution (4

µ

A)) - offset value (1000)

Example

When outputting 18 mA

(18000 (µA) ÷ 4 (µA)) - 1000 = 3500

Write "3500" to data memory for D/A conversion.
Next, turn ON the special utility relay for D/A conversion.

Resolution

"Resolution" refers to the minimum analog output value by which digital data can be
changed. For example, 5 mV is the resolution of output range -10 to +10 V. This
indicates that the analog output changes by 5 mV when the value of the digital data
changes by 1.

Digital data content

The KV-DA4 voltage and current output characteristics are as follows.

For example, the digital data for outputting +5 V is 3000.

Digital
data

+1000

+2000

+3000

+4000

+10

-8

-6

-4

-2

0

+2

+4

+6

+8

Range: ±10 V

-10

Voltage
(V)

Voltage output characteristics

Digital
data

+1000

+2000

+3000

+4000

0

2

6

8

10

12

14

16

18

Current
(mA)

20

4

Range: 4 to 20 mA

Current output characteristics