7.7 Non-procedure Mode Programming

KV-300 Series Only

KV

-300

KV-10/80

Chapter 7 KV-L2 Serial Interface Module

1-299

1

7

2. First relay no. +1

Turns ON and remains ON when the loaded data cannot be transferred to data
memory because the first relay no. +0 is ON when the data is received, or a parity
error has occurred (that is, first relay no. +2 was ON) during data reception.
When the data is loaded while the first relay no. +1 is ON, the first relay no. +1 turns
OFF when the first relay no. +0 turns ON.
To fetch the ON signal only for one scan, change the program as shown in 1. First
relay no. +0, above.

3. First relay no. +2

Turns ON and remains ON when the data cannot be received because a parity error
has occurred during data reception. (The first relay +0 turned ON simultaneously.)
When the data is loaded while the first relay no. +2 is ON, the first relay no. +2 turns
OFF when the first relay no. +0 turns ON.
To fetch the ON signal only for one scan, change the program as shown in 1. First
relay no. +0, above.