8.5 KV-AN6 Appendices

KV-300 Series Only

KV

-300

KV-10/80

Chapter 8 KV-AN6 Analog I/O Module

1-330

8

8.5.2

Precautions

Environmental requirements

When installing the KV-AN6, note the following:

•

Avoid exposure to direct sunlight.

•

Avoid exposure to temperatures below 0°C (32°F) or exceeding 50°C (122°F).

•

Avoid exposure to humidity below 35%RH or exceeding 85%RH.

•

Avoid areas where condensation occurs due to sudden drops in temperature.

•

Avoid exposure to corrosive or flammable gases.

•

Avoid exposure to airborne dust, metal particles, oil, or corrosive substances
such as salt.

•

Avoid exposure to strong vibration or impact.

•

Avoid locations where water, oil, or chemicals may splash the KV-AN6.

•

Avoid exposure to strong magnetic or electrical fields.

Panel installation

Consider accessibility and environmental resistance when installing the KV-AN6
inside a panel.

Ambient temperature

The operating temperature range of the KV-AN6 is 0 to 50°C (32 to 122°F) (No
freezing).
Provide enough space for proper ventilation.
if the temperature exceeds 50°C (122°F), provide a fan or air conditioner.

Improving noise resistance

Do not install the KV-AN6 and high-voltage equipment in the same control panel.
Isolate the KV-AN6 as far as possible from power cables.

Access

Isolate the KV-AN6 as far as possible from high voltage equipment and drive
equipment to ensure safe and easy access for adjustment and maintenance.

Wiring

The KV-AN6 terminal block includes M3.0 screws.
Use the following types of crimp terminals.

6.0 max.

6.0 max.

KVHKA Chap 08.p65

08.3.11, 11:19 AM