n078:

Multi Function Analog Input Signal Selection

n079:

Frequency Reference Bias Setting

This bias is used only for the auxiliary analog input.

Factory Setting:

10%

Range: 0 to 50%

Factory Setting:

0

Range: 0 or 1

Setting

Description

0

2CN input terminal (0-10V input)

1

2CN input terminal (4-20mA input)

3) Frequency Reference Bias (n077=3)

FBIAS is added to the frequency reference, after
frequency reference gain (n060 (terminal FR) or
n074 (terminal RP)) and frequency reference bias
(n061 (terminal FR) or n075 (terminal RP)) are used
to calculate master speed reference input at
terminals FR or RP

Continued

5.32 MULTI-FUNCTION ANALOG INPUT SELECTION

4) Output Voltage Bias (n077=4)

VBIAS is added to output voltage after V/f pattern
is established