Example 5: Remote Sequence (3-Wire) & Speed Potentiometer

This configuration is best when a person rather than an external controller (PLC, relay, etc.) controls the drive.
Both potentiometers ((R1) & (R2)) should have a resistance value between 2000

Ω and 3000Ω and be rated for

at least 1 Watt. The trim pot is optional, but without it the manual speed pot will output 10V (60 Hz) at just
three-quarters of its rotation.

OPERATION:
• Close pushbutton (PB1) momentarily while pushbutton (PB2) is closed and the drive will start.

Pushbutton (PB1) does

NOT need to be maintained.

• Open pushbutton (PB2) at any time and the drive will stop.
• If switch (SW1) is open the drive will run in the forward direction. If switch (SW1) is closed, the drive will

run in the reverse direction. Switch (SW1) can be operated with the drive running at any speed.

• Frequency reference is proportional to the signal level at Terminal FV.

0V = 0 Hz, 5V = 30 Hz, & 10V = 60 Hz.

• If the drive is put in the “Local” mode using the LO/RE quick start LED, the drive will behave the same as

illustrated in Example 1.

Table 6: Programming Required For Remote 3-wire Sequence & Speed Pot Reference

After the programming is complete, the trim pot needs to be calibrated. Press DSPL until the FREF quick start
LED is illuminated. Turn the Speed Pot (R1) all the way up. Adjust the trim pot (R2) so that the “Frequency
Reference” display is just flickering between 59.99 Hz and 60.00 Hz. This completes the trim pot calibration.

FR

FC

FREQUENCY
REFERENCE
0 - 10V DC

ANALOG
COMMON

Speed Pot

(R1)

2.5K

2.5K

Optional

Trim Pot

(R2)

DATA
ENTER

DSPL

RUN

MIN

MAX

STOP

FOR/REV

START

Start

Stop

Forward

(SW1)

(PB2)

(PB1)

Reverse

S1

S2

S3

S4

S5

S6

S7

SC

STOP

RESET

FREF

FOUT

IOUT

MNTR

PRGM

LO/RE

F/R

Shield (Drain Wire)

To Terminal

Control Wiring Schematic

0. 0 0

FS

+12 VDC

Parameter

Display

Description

n001

11

n001

4

n036

Set Motor FLA

The drive will perform a 3-wire reset.

Setting this value will reset all parameters to their original factory
settings (all previous adjustments will be lost).

When the drive

completes the reset, this parameter returns to a value of 1.

CAUTION

After doing the reset above, the password parameter returned to a
1. Change it to a 4 to get access to all parameters in the drive.
Enter the motor’s full load amps as shown on the motor nameplate.