A6-3 – Yaskawa V7 Drives User Manual

Page 141

Advertising
background image

A6-3

Figure A6-1. Typical Wiring of Braking Resistor

(for 3% Duty Cycle) to Drive

THERMOSTAT
OR OVERLOAD

BRAKING
RESISTOR
(3% DUTY
CYCLE)

SEPARATE CUSTOMER
SUPPLIED ENCLOSURE
AND THERMISTOR
OR OVERLOAD

PART OF CUSTOMER
SUPPLIED EXTERNAL
CIRCUIT

CONTROL

TERMINAL BLOCK

NOTE 2

NOTE 1

NOTES:

(1) Wire in series with any other external fault

N.O. contacts connected to the Drive.

(2) Factory default is terminal S3 programmed

for external fault N.O. contact input (2-wire
control). If S3 has been reprogrammed to
another function, one of the other multi-
function terminals must be programmed
for external fault N.O. contact input.

For 3-wire control, connect to one of the
other multi-function input terminals and
program that terminal for external fault
N.O. contact input.

(3) Either an overload can be used in series with

the Braking resistor or a thermostat can be
configured as shown.

POWER

ON

POWER

OFF

1M

1M

FAULT

CONTACT

RC

RC

120 VAC

THRX

THRX

THRX

THRX

S3

CB

L3

1M

L2

1M

L1

1M

SC

B2

T1

T2

T3

L1(R) L2(S) L3(T)

B1

OVERLOAD

NOTE 3

NOTE 3

V7N

T1(U) T2(V) T3(W)