1-12

E. Conformance to European EMC Directive

In order to conform to EMC standards, the following methods are required for line filter application,

cable shielding and drive installation.

The line filter and Drive must be mounted on the same metal plate. The filter should be mounted as

close to the drive as practical. The cable must be kept as short as possible and the metal plate

should be securely grounded. The ground of the line filter and the drive must be bonded to the

metal plate with as much bare-metal contact as possible.

For main circuit input cables, a screened cable is recommended within the panel and is also

suggested for external connections. The screen of the cable should be connected to a solid ground.

For the motor cables, a screened cable (max. 20 m) must be used and the screen of the motor cable

should be connected to ground at both ends by a short connection, again using as much bare-metal

contact as practical.

For a more detailed explanation, refer to the manufacturer document EZZ006543, “Installation

Guidelines For EMC Directive using AC Drive Products.”

Table 1-4 and Figure 1-4 show the line filter list for EMC standards and the installation/wiring of the

Drive and line filter.

Model

Line Filter

CIMR-

Part Number

Rated

Weight

Dimensions in in. (mm)

Mounting Dim. in in. (mm)

Screw

V7*

MV

FIL00

Current (A)

lbs. (kg)

H x W x D

(1)

H1 x W1

Size

20P1

A001

20P2

A002

20P4

A003

1083

10

1.8 (0.8)

7.6 x 3.2 x 2.0 (194 x 82 x 50)

7.1 x 2.4 (181 x 62)

M5

20P7

A005

21P5

A008

1084

16

2.2 (1.0) 6.7 x 4.4 x 2.0 (169 x 111 x 50)

6.1 x 3.6 (156 x 91)

M5

22P2

A011

23P7

A017

1085

26

2.4 (1.1) 6.9 x 5.7 x 2.0 (174 x 144 x 50)

6.3 x 4.7 (161 x 120)

M5

25P5

A025

1100

50

5.1 (2.3) 12.0 x 7.2 x 2.2 (304 x 184 x 56) 11.3 x 5.9 (288 x 150)

M6

27P5

A033

40P2

B001

1086

5

2.2 (1.0) 6.7 x 4.4 x 1.8 (169 x 111 x 45)

6.1 x 3.6 (156 x 91)

M5

40P4

B002

40P7

B003

41P5

B005

1087

10

2.2 (1.0) 6.7 x 4.4 x 1.8 (169 x 111 x 45)

6.1 x 3.6 (156 x 91)

M5

42P2

43P7

B009

1088

15

2.4 (1.1) 6.9 x 5.7 x 2.0 (174 x 144 x 50) 6.3 x 4.7 (161 x 120)

M5

45P5

B015

47P5

1101

30

5.1 (2.3) 12.0 x 7.2 x 2.2 (304 x 184 x 56) 11.3 x 5.9 (288 x 150)

M6

(1)

D is the distance the filter will extend outward from the surface of the metal plate.

Continued

1.4 ELECTRICAL INSTALLATION

W1

W

H1

H

D

4-d

Table 1-4. Line Filters for EMC Standards

Advertising