6-2

Alarm Display

Digital

RUN (Green)

Drive

Explanation

Causes and

Operator

ALARM (Red)

Status

Corrective Actions

CAL (MODBUS

Check communication

communications waiting)

devices, and transmission

Correct data has not been

signals.

received from the PLC
when the parameter
n003 (operation command

Blinking

selection) is 2 or
n004 (frequency reference
selection) is 6,
and power is turned ON.

OPE

(Parameter setting

Check the setting values.

error when the parameter
setting is performed
through the MODBUS
communications)
OPE1: Two or more values

are set for multi-
function input
selection.
(parameters n050 to
n056)

OPE2: Relationship among

V / f parameters is not
correct.
(parameters n011,
n013, n014, n016)

Blinking

OPE3: Setting value of

electronic thermal
standard current
exceeds 150% of
drive rated current.

Warning

(parameter n036)

only.

OPE4: Upper / lower limit

Fault

of frequency

contacts

reference is reversed.

do not

(parameters n033,

change

n034)

state.

OPE5: (parameters n083 to

n085)

OPE9: Carrier frequency

setting is incorrect.
(parameter n080)

OL 3 (Overtorque

Reduce the load, and

detection)

increase the accel / decel

Motor current exceeded

time.

the preset value in

Blinking

parameter n098.

SEr (Sequence error)

Check the external circuit

Drive receives

(sequence).

LOCAL / REMOTE select
command or

Blinking

communication / control
circuit terminal changing
signals from the multi-
function terminal while the
drive output is ON.

Table 6-1. Alarm Displays and Corrective Actions - Continued