A1-7, Table a1-1. drive parameters - continued – Yaskawa V7 Drives User Manual

Page 127

Advertising
background image

A1-7

PARA-

SETTING RANGE

SETTING

FACTORY

USER

PARA.

METER

NAME

(AND UNITS)

INCREMENT

SETTING

SETTING

REF.

0:

0.1 Hz

n152

Modbus Frequency

1:

0.01 Hz

Reference Unit2:

30000/100%

1

0

3:

0.1 %

n153

Modbus Slave Address

0 to 32

1

0

0:

2400 bps

n154

Modbus Baud Rate

1:

4800 bps

5.14

2:

9600 bps

1

2

3:

19200 bps

0:

even parity

n155

Modbus Parity Selection

1:

odd parity

1

2

2:

no parity

n156

Modbus Send Waiting Time

10 to 65

1 (msec)

10

0:

RTS control enabled

n157

Modbus RTS control

1:

RTS control disabled 1

0

(RS-422A 1 to 1 communication)

n158

Motor Code

0 to 70

1

(Note 1)

n159

Energy Saving Voltage
Upper Limit At 60 Hz

0 to 120

1%

120

(Energy Saving)

n160

Energy Saving Voltage
Upper Limit At 6 Hz

0 to 25

1%

16

(Energy Saving)

5.31

n161

Power Supply Detection

0 to 100

1%

10

Hold Width (Energy Saving)

n162

Power Supply Detection

0 to 255

1

5

Filter Time Constant

(x 4 ms)

(20 ms)

n163

PID Output Gain

0.0 to 25.0

0.1

1.0

0:

Terminal FR (Voltage 0 - 10V)

1:

Terminal FR (Current 4 - 20mA)

2:

Terminal FR (Current 0 - 20mA)

n164

PID Feedback Selection

3:

Multi-Function Analog Input

1

0

5.28

(Voltage 0 - 10V)

4:

Multi-Function Analog Input
(Current 4 - 20mA)

5:

Pulse input

n166

Input Phase Loss

0 to 100 (%)

1%

0

Detection Level

n167

Input Phase Loss

0 to 255 (sec)

1 sec

0

Detection Time

n168

Output Phase Loss

0 to 100 (%)

1%

0

Detection Level

n169

Output Phase Loss

0.0 to 2.0 (sec)

0.1 sec

0

Detection Time

n173

DC Injection P Gain

1 to 999

1 (0.001)

83 (0.083)

n174

DC Injection I Time

1 to 250

1 (4ms)

25

(100ms)

n175

Reduce Carrier

0:

Disabled

at low speed selection

1:

Carrier Frequency reduced to 2.5kHz

1

0

5.5

when Fout <= 5Hz & Iout >= 110%

rdy : READY status

rdy

rEd: READ executes

rEd

n176

Digital Operator Parameter

Cpy: COPY executes

Cpy

rdy

5.29

Copy Function Selection

vFy: VERIFY executes vFy
vA:

Inverter capacity display

vA

Sno: Software No. displaySno

n177

Digital Operator

0:

Read disabled

Parameter copy

1:

Read allowed

1

0

5.29

Access Selection

n178

Fault History

(Note 3)

N/A

N/A

6.2

n179

Software Number

(Note 3)

N/A

N/A

4.4

Table A1-1. Drive Parameters - Continued

Note 1: Factory setting differs depending on V7 capacity. See Appendix 3-1.
Note 2: Factory setting differs depending on control method selected (n002). See Appendix 3-1.
Note 3: n178 and n179 are display only parameters
Note 4: Parameter can be changed while V7 is operating.