n092 : Stall Prevention During Deceleration

Factory setting:

0

Setting

Function

0

Stall prevention during deceleration enabled

1

Stall prevention during deceleration disabled

Stall prevention during deceleration automatically
adjusts the deceleration rate while monitoring the
DC bus voltage to prevent overvoltage during
deceleration.

When the motor load is large or decel time is
short, actual decel time may be longer than the
set value because of stall prevention

.

B.

n093 : Stall Prevention Level During

Factory setting: See Table A3-1

Acceleration

Range: 30 - 200 %

This parameter determines the actual Drive output current level during an acceleration condition. Set in
percent of Drive rated output current.

A setting of " 200 " disables stall
prevention during acceleration. During
acceleration, if the output current
exceeds the value in

n093 , acceleration

stops and frequency is maintained.
When the output current goes below the
value set in

n093 , acceleration resumes.

In the constant horsepower region
[actual output frequency

≥ max. voltage

frequency (

n013 )], the stall prevention

level during acceleration is changed by
the following formula:

Stall prevention level during

= Stall prevention level during accel x

Max. voltage frequency

accel (constant horsepower)

Actual output frequency

5.23 STALL PREVENTION

TIME

FREQUENCY

SET
DECEL
TIME

Controls the
deceleration
time needed to
prevent over-
voltage fault.

C.

n094 : Stall Prevention Level At Set Speed

Factory setting:

160%

Range: 30 - 200 %

This parameter determines the actual
Drive output current level while operating
at set speed (frequency). Set in percent
of Drive rated output current (see
Appendix 2).

A setting of " 200 " disables stall
prevention at set speed. During running
at set speed, if the output current exceeds
the value set in

n094 , the drive will begin

to decelerate. When the output current
goes below the value set in

n094,

acceleration begins, up to the set
frequency.

t

t

MOTOR
CURRENT

OUTPUT
FREQ.

Constant

n074

setting

Parameter
n094
Setting

t

t

MOTOR
CURRENT

OUTPUT
FREQ.

Constant

n073

setting

Parameter
n093
Setting