3 accel/decel: s-curve characteristics, Accel/decel: s-curve characteristics -3 – Yaskawa V7 Drives User Manual

Page 55

Advertising
background image

5-3

n023 : S-Curve Selection

Factory setting:

0

Range: 0 to 3

Setting of this parameter
determines the S-curve
(starting) characteristics
of the acceleration ramp.

0 = S-curve disabled
1 = S-curve

of 0.2 seconds

2 = S-curve time

of 0.5 seconds

3 = S-curve time

of 1.0 seconds

NOTE: Actual accel time = Set accel time + (2

*

S-curve selection)

Actual decel time = Set decel time + (2

*

S-curve selection)

The following figure shows FWD/REV switching and acceleration & deceleration to a stop with
S-curve active.

RUN

FREQ

COMMAND

0

TIME

S-Curve Characteristics

Time (T

SC

)

OUTPUT

FREQUENCY

Accel ramp per
selected Accel Time
(

n019 or n021 )

5.3 ACCEL/DECEL: S-CURVE CHARACTERISTICS

FORWARD RUN COMMAND

= S-CURVE CHARACTERISTIC

MIN. OUTPUT
FREQUENCY
n016

DC INJECTION
TIME AT STOP
n090

DECELERATION

DECELERATION

REVERSE RUN COMMAND

OUTPUT FREQUENCY

ACCELERATION

ACCELERATION

n016

Advertising
This manual is related to the following products: