The Drive control circuits use various parameters to select functions and characteristics of the
Drive. Changing of parameter settings must be done in the Program mode, or by use of the
Function LEDs, if available (see Section 4).

The following table lists all parameters in numerical order. For each parameter, reference
paragraph(s) in Section 5 are listed (if applicable) where the features of the Drive affected by that
parameter are described.

Appendix 1. PARAMETER LISTING

PARA-

SETTING RANGE

SETTING

FACTORY

USER

PARA.

METER

NAME

(AND UNITS)

INCREMENT

SETTING

SETTING

REF.

0:

n001 can be read and set;
n002 - n179 read only

1:

n001 - n039 can be read and set

2:

n001 - n079 can be read and set

3:

n001 - n119 can be read and set

n001

Parameter Selection /

4:

n001 - n179 can be read and set

Initialization

5:

n001 - n179 can be read and set

1

1

5.21

Run command accepted during Program mode

6:

Clear Fault History Only

7:

Not Used

8:

2-wire Initialization (Japan Spec.)

9:

3-wire Initialization (Japan Spec.)

10: 2 wire initialization (USA Spec)
11: 3 wire initialization (USA Spec.)

n002

Control Method Selection

0:

V/f Control

1

0

2.2

1:

Open Loop Vector

0:

Digital Operator

n003

Operation Method Selection

1:

Terminal

1

1

5.13

2:

Serial Communication (Modbus)

3:

Option Card

0:

Digital Operator Pot

1:

Digital Operator

2:

Voltage Reference (0 to 10V)

3:

Current Reference (4 to 20 mA)

n004

Reference Selection

4:

Current Reference (0 to 20 mA)

5.11,

5:

Pulse Train Reference

1

2

5.13

6:

Serial Communications (Modbus)

7:

Multi-Function Analog Input (0 to 10V)

8:

Multi-Function Analog Input (4 to 20 mA)

9:

Option Card

n005

Stop Method

0:

Ramp to stop

1

0

5.24

1:

Coast to stop

n006

Reverse Prohibit

0:

Reverse Run enabled

1

0

1:

Reverse Run disabled

0:

STOP key is effective regardless of
programming of n003

n007

STOP Key Function

1:

STOP key is effective only when sequence

1

0

5.13

command (per n003) is from Digital Operator

0:

Frequency Reference from digital

n008

Reference Selection -

operator pot

1

0

5.13

Digital Operator

1:

Frequency Reference from n024

0:

ENTER key must be pressed to write-in

n009

Frequency Reference Setting

new value

1

0

5.13

Method From Digital Operator

1:

ENTER key does not have to be pressed
to write-in new value

Operation Selection

0:

Disabled (operation continues)

n010

When Digital Operator is

1:

Enabled (motor coasts to a stop and fault

1

0

5.15

Disconnected

is displayed)

n011

Frequency - Max.

50.0 to 400.0

0.1 (Hz)

60.0

n012

Voltage - Max.

0.1 to 255.0 (230V drive)

0.1 (V)

230.0

0.2 to 510.0 (460V drive)

460.0

n013

Frequency - Max.

0.2 to 400.0

0.1 (Hz)

60.0

Voltage Point

n014

Frequency - Midpoint

0.1 to 399.9

0.1 (Hz)

(Note 2)

5.27

n015

Voltage - Midpoint

0.1 to 255.0 (230V drive)

0.1 (V)

(Note 2)

0.2 to 510.0 (460V drive)

n016

Frequency - Min.

0.1 to 10.0

0.1 (Hz)

(Note 2)

n017

Voltage - Min.

0.1 to 50.0 (230V drive)

0.1 (V)

(Note 2)

0.2 to 100.0 (460V drive)

Table A1-1. V7 Parameters