Current ratings and horsepower range, Warning caution – Yaskawa V7 Drives User Manual

Page 17

Advertising
background image

- xv -

Do not touch circuit components until main input power has been turned
OFF. Status indicator LEDs and Digital Operator display will be extinguished
when the DC bus voltage is below 50 VDC. Wait 5 additional minutes.

Do not connect or disconnect wires and connectors while the main input
power is turned on.

(1)

47P5 drive, with a current rating of 21.0 A and nominal horsepower of 15, is only
available as a V74X drive.

The Drive leaves the factory with parameters initialized for 2-Wire control
(when using external Run/Stop signals). Before using the initialization
function of constant n001, know your control wiring configuration:

10 = Factory 2-Wire Control Initialization (Maintained RUN Contact)
11 = Factory 3-Wire Control Initialization (Momentary START/STOP Contact)

Entering either Initialization code resets all parameters to factory settings,
and automatically returns parameter n001 setting to “ 1 ”. If the Drive is
connected for 3-Wire control and this parameter is set to “ 10 ” (2-Wire
Control Initialization), the motor may run in reverse direction WITHOUT A
RUN COMMAND APPLIED. Equipment damage or personal injury may
result.

WARNING

CAUTION

Rated

Current

Nominal

Model Number

Input Voltage

Rating [A]

Horsepower

CIMR-V7*

MV

0.8

1/8

20P1

A001

1.6

1/4

20P2

A002

3.0

1/2

20P4

A003

5.0

3/4 & 1

20P7

A005

230V

8.0

2

21P5

A008

11.0

3

22P2

A011

17.5

5

23P7

A017

25.0

7.5

25P5

A025

33.0

10

27P5

A033

1.2

1/2

40P2

B001

1.8

3/4

40P4

B002

3.4

1 & 2

40P7

B003

460V

4.8

3

41P5

B005

5.5

3

42P2

8.6

5

43P7

B009

14.8

7.5 & 10

45P5

B015

18.8

10

47P5

21.0

(1)

15

(1)

47P5

(1)

Current Ratings & Horsepower Range