5.27 V/f PATTERN

The V/f pattern can be tailored to suit your specific application and load characteristics by adjusting
parameters

n011 to n017 (see the V/f characteristics figure on the following page).

NOTES:

1

VT = Variable Torque, typically used for blowers, centrifugal pumps, and fans.
CT = Constant Torque, most other applications. Consult the manufacturer for further assistance.

The following conditions must be considered when selecting a V/f pattern:

- Pattern matches the voltage-frequency characteristics of the motor.
- Maximum motor speed.

2

V/f pattern for high starting torque should be selected for:

- Long wiring distance.
- Large voltage drop at start
- AC reactor connected to Drive input or output.
- Use of motor rated below Drive max. output.

3

Voltages shown are for 230V motors; for other motor voltages, multiply all voltage (V) values by (Vmtr/230).
i.e., for a 460V motor, multiply by 460/230 = 2.

Max.

Starting

Load

n011

n012

n013

n014

n015

n016

n017

Freq.

Torque

Type

1

(Hz)

(V)

3

(Hz)

(Hz)

(V)

3

(Hz)

(V)

3

50

Normal

VT

50

230

50

25.0

40.2

1.3

9.2

50

High

2

VT

50

230

50

25.0

57.5

1.3

11.5

60

Normal

VT

60

230

60

30.0

40.2

1.5

9.2

60

High

2

VT

60

230

60

30.0

57.5

1.5

11.5

50

Normal

CT

50

230

50

3.0

17.2

1.5

11.5

50

Medium

CT

50

230

50

2.5

23.0

1.3

13.8

50

High

2

CT

50

230

50

2.5

28.7

1.3

16.1

60

Normal

CT

60

230

60

3.0

17.2

1.5

11.5

60

Medium

CT

60

230

60

3.0

20.7

1.5

13.8

60

High

2

CT

60

230

60

3.0

28.7

1.5

23.0

72

Normal

CT

72

230

60

3.0

17.2

1.5

11.5

90

Normal

CT

90

230

60

3.0

17.2

1.5

11.5

120

Normal

CT

120

230

60

3.0

17.2

1.5

11.5

180

Normal

CT

180

230

60

3.0

17.2

1.5

11.5

Table 5-4. Recommended V/f Patterns