n095 : Speed Coincidence Frequency / Frequency

Factory setting:

0.0 Hz

Detection Level

Range: 0.00 to 400.0 Hz

Speed coincidence is used to control an output contact at terminals MA or MB (with respect to ter-
minal MC), or terminals P1, P2 & PC, when selected by

n057, n058 and n059.

n057, n058 or n059

Data

2 , 4 or 5

The output contact will close, dependent upon the data programmed into

n057, n058 or n059 . See

the appropriate figure below for operation.

A. Speed at Set Frequency

B.

Frequency Detection – Low

(setting:

n057, n058

or

n059

= " 2 ")

(setting:

n057, n058

or

n059

= " 4 ")

C. Frequency Detection – High

(setting:

n057, n058

or

n059

= " 5 ")

5.19 MULTI-FUNCTION OUTPUT TERMINALS

ON

FREQUENCY

AGREED

SIGNAL

OUTPUT

FREQUENCY

DETECTION WIDTH

±2Hz

±2Hz

RELEASE WIDTH

Frequency
Reference

FREQUENCY

FREQUENCY
DETECTION
LEVEL (Hz)
(n095 )

RELEASE WIDTH

+2HZ

FREQUENCY

DETECTION

SIGNAL

ON

ON

RELEASE WIDTH

—2HZ

FREQUENCY
DETECTION
LEVEL (Hz)
(n095)

OUTPUT

FREQUENCY

FREQUENCY

DETECTION

SIGNAL

Advertising