Caution warning – Yaskawa V7 Drives User Manual

Page 34

Advertising
background image

1-16

NOTES FOR FIGURE 1-6

– Indicates components not supplied.

– Main circuit terminal.

– Indicates control circuit terminal.

( ) – Indicates alternate terminal marking, i.e., (R) and L1.

– Function labels shown for these terminals are determined by factory settings of

n050

through

n056 (see paragraph 5.18).

– Function labels shown for these terminals are determined by factory settings of

n057 through n059

(see paragraph 5.19).

– Function label shown for this terminal is determined by factory setting of

n004 (see paragraph 5.11A).

– Function labels shown for these terminals are determined by factory setting of

n066 (see paragraph 5.17).

1.

Insulated twisted shielded wire is required.

2-conductor #18 GA. (Belden #8760 or equivalent)
3-conductor #18 GA. (Belden #8770 or equivalent)

Connect shield only at the Drive end (ground terminal ( ) ). Stub and isolate other end.

2.

+12V voltage output current capacity of control terminal FS is 20mA max.

3.

The Drive’s Electronic Thermal Overload function (

n036, n037) meets standards set by UL and CUL for motor thermal

overload protection. If local code requires a separate mechanical overload protection, an overload relay should be
installed, interlocked with the Drive as shown. It should be the manual reset type to prevent automatic restart following
a motor fault and subsequent contact reclosure after cool down.

4.

Customer to connect ground terminal ( ) to earth ground.

5.

If Digital Operator is used, remote operators which duplicate functions of its command keys (see Figure 4-1) may not
be required.

6.

For installation of Braking Resistor or Braking Resistor Unit, refer to Appendix 6, “Dynamic Braking Option”.

7.

An optional DC reactor may be added for harmonic attenuation, if needed; see separate instruction sheet for wiring.

8.

If application does not allow reverse operation, parameter

n006 , Reverse Run Prohibit Selection, should be set to “ 1 ”

(Reverse Run Disabled) and Fwd/Rev input can be eliminated.

9.

Input fuses are required for proper branch circuit short circuit protection for all NEMA type 4 drives. Failure to
use recommended fuses (see appendix 4) may result in damage to the drive and/or personal injury.

Parameter

n050 must be set to “ 0 ”, AND parameter

n001 must be set to “ 11 ”. Resetting drive parameter
n001 to “ 10 ” may cause the motor to run in reverse
direction WITHOUT A RUN COMMAND, and possibly result
in equipment damage or personal injury.

G. Interconnection - 3 Wire

Continued

1.4 ELECTRICAL INSTALLATION

CAUTION

WARNING