5-7

n016 : Minimum Frequency

Range: 0.1 to 10.0 Hz

n089 : DC Injection Braking Current

Factory setting:

50 %

(% of Drive Rated Current)

Range: 0 to 100 %

n090 : DC Injection Time at Stop

Factory setting:

0.5 sec

Range: 0.0 to 25.5 sec

n091 : DC Injection Time at Start

Factory setting:

0.0 sec

Range: 0.0 to 25.5 sec

DC injection can be used to stop a motor whose rotational direction is uncertain at start-up, or to
help stop a coasting motor.

With ramp to stop enabled (

n005 = " 0 " ), after a STOP command is received the Drive controls

motor deceleration according to the Decel Time setting, until output frequency reaches the DC
injection braking start frequency (or Minimum Frequency,

n016 ). Then the Drive output is turned off

and DC injection current is applied to the motor. The effective DC injection time and current should
be set to provide adequate stopping without excessive motor heating. The DC injection voltage is
determined by the DC injection braking current and motor impedance.

DC Braking Sequence

5.7 DC INJECTION BRAKING

RUN COMMAND

OUTPUT FREQUENCY

STOP

RAMP TO STOP

DC

DC

DC INJECTION TIME AT

START (

n091 )

MINIMUM

FREQUENCY (

n016 )

DC INJECTION TIME AT

STOP (

n090 )