Table 5-3. multi-function output terminals – Yaskawa V7 Drives User Manual

Page 81

Advertising
background image

5-29

Set

Description

Value

Condition

Signal Level

0

Fault

Closed = Drive fault has occurred (except CPF00, CPF01)

1

During operation

Closed = Drive is operating

2

Speed at set frequency

Closed = Frequency Reference = output frequency
See paragraph 5.19A

3

Zero Speed

Closed = Drive is at zero Hz.

4

Frequency detection - low

Closed = Output frequency

n095.

See paragraph 5.19B

5

Frequency detection - high

Closed = Output frequency

n095.

See paragraph 5.19C

6

Overtorque detection

Closed = Overtorque detected

(N.O. contact)

See paragraph 5.20

7

Overtorque detection

Open = Overtorque detected

(N.C. contact)

See paragraph 5.20

8

Under torque detection (NO)

Closed if under torque is detected

9

Under torque detection (NC)

Open if under torque is detected

10

Alarm (minor fault)

Closed = Alarm condition is present

11

During coast to stop

Closed = Drive output base block is active; motor is coasting

12

Local/Remote

Open = Frequency and Run Command by ext. input;
Closed = Frequency and Run Command by Digital Operator

13

Operation ready

Closed = Drive is ready for operation (not faulted)

14

Auto-restart

Closed = During auto-restart operation

15

During Undervoltage

Closed = Drive has an undervoltage fault or warning.

16

During Reverse run

Closed = Drive operation in reverse

17

During Speed Search

Closed = Drive performing a speed search

18

Serial communication

Closed = Command from serial communication

20

Frequency reference is missing

Closed if frequency reference is missing

21

Inverter overheating pre-alarm OH3

Closed if drive overheat pre-alarm is input at a Multi-function
Input. Digital operator display is “OH3” (blinking)

Table 5-3. Multi-function Output Terminals