Important – Yaskawa V7 Drives User Manual

Page 80

Advertising
background image

5-28

n057 : Contact Output (external

terminals MA, MB, & MC)

n058 : Open Collector Output

(external terminals P1 & PC)

n059 : Open Collector Output

(external terminals P2 & PC)

A contact, or two different open collector outputs,
can be programmed to change states during any of
the conditions indicated in Table 5-3.

IMPORTANT

If an open collector output is applied to a DC relay, the relay MUST be diode
protected, as shown in the recommended configuration below.

5.19 MULTI-FUNCTION OUTPUT TERMINALS (Term. MA, MB, MC, P1, P2, PC)

P1

P2

PC

o o

MULTI-FUNCTION
CONTACT OUTPUT
250Vac 1A OR LESS
30Vdc 1A OR LESS
(FACTORY SETTING
IS FOR SIGNAL
DURING OPERATION)

MULTI-
FUNCTION
OPEN
COLLECTOR
OUTPUTS
48Vdc AT
50mA MAX.

Recommended
Configuration for
DC Relays

P1

P2

PC

C

DC
RELAY

DIODE

48Vdc MAX. *

*

*

* Customer

supplied

MA

o o

MB

MC

Drive

Advertising
This manual is related to the following products: