n036 : Motor Rated Current

Factory setting: See Table A3-1

Range: see description

This parameter should be set, in increments of 0.1 A, to the rated current (FLA) value shown on the motor
nameplate; this value MUST BE between 10% and 150% of the

drive rated current. If the motor FLA does not

fall within this range, a different Model No. drive must be used.

NOTE: Setting

n036 to " 0.0 " disables the motor overload protection

function, regardless of the setting of

n037 or n038.

n037 : Electronic Thermal Motor Protection

Factory setting:

0

Range: 0 to 2

Setting

Electronic Thermal Characteristics

0

Short term rating

1

Standard rating

2

Electronic thermal overload protection disabled

n038 : Electronic Thermal Overload Protection

Factory setting:

8

Time Constant

Range: 1 to 60 min.

This parameter sets the electronic thermal overload relay protection time when when 150% of overload is
applied after the motor is operated continuously at rated current.

The Drive protects against motor overload with a UL-recognized, built-in electronic thermal overload relay.

The electronic thermal overload function monitors motor temperature, based on drive output current and time,
to protect the motor from overheating. When the electronic thermal overload trips, an
oL1 ” error occurs, shutting OFF the drive output and preventing excessive overheating of the motor.

When operating with one drive connected to only one motor, an external thermal relay is not needed. When
operating several motors with one drive, install a thermal overload relay on each motor.

5.25 THERMAL OVERLOAD PROTECTION

Electronic Thermal

Cooling Effect

Current Characteristics

Overload

Effective when
operated at 60Hz
from a commercial
power supply

oL 1

” error (motor

overload protection)
occurs when
continuously operated
at less than 60Hz at
100% load.

Base Frequency

60Hz

(V/f for 60Hz,

230V Input Voltage)

0

38

55

80

100

TORQUE

(%)

140

155

180

3 20

60

120

60 SEC
SHORT TERM

CONTINUOUS
RATING

OPERATION FREQUENCY (Hz)

Effective when
operated at low
speed (approx. 6Hz)

Electronic thermal
overload protection not
activated even when
continuously operated
at less than 60Hz at
100% load.

0

38

55

100

TORQUE

(%)

150

180

6

60

120

OPERATION FREQUENCY (Hz)

60 SEC
SHORT TERM

CONTINUOUS
RATING

Shor

t T

er

m

Rating

Standard Rating

Base Frequency

60Hz

(V/f for 60Hz,

230V Input Voltage)

5-38