DATA

FUNCTION

DESCRIPTION*

S1

Multi-Function-Input 1

Factory setting is "

Forward Run/Stop " (1).

(Forward run when closed, stop when open)

S2

Multi-Function-Input 2

Factory setting is "

Reverse Run/Stop " (1).

(Reverse Run when closed, stop when open)

S3

Multi-Function-Input 3

Factory setting is "

External Fault (NO contact)

input " (1)

S4

Multi-Function-Input 4

Factory setting is "

Fault Reset " (1)

S5

Multi-Function-Input 5

Factory setting is "

Multi-step Speed

Reference 1 " (1)

S6

Multi-Function-Input 6

Factory setting is "

Multi-step Speed

Reference 2 " (1)

S7

Multi-Function-Input 7

Factory setting is "

Jog Reference" (1)

SC

Sequence common for terminals S1-S7.

Common terminal for sequence inputs

FS

Frequency reference power supply

+12 VDC

FR

Frequency reference input

0 to +10V/100% (20K ohms) or 4-20 mA (250

Ω)

RP

Frequency reference –Pulse Train input

30 KHz maximum pulse input

FC

Frequency reference input common

0 V

MA

Multi-function contact output – NO contact

Factory

Contact capacity:

MB

Multi-function contact output – NC contact

Setting

250 Vac at 1A or below

MC

Multi-function contact output – Common

is " Fault "

30 Vdc at 1A or below

AM

Multi-function analog monitor (+) Factory setting is

"

Output frequency "

0-10V = 0-100%

Monitor output: 0 to +10V; 2 mA maximum.

AC

Analog monitor common

0 V

P1

Multi-Function Open

Factory setting is

Collector Output 1

"

Drive Running "

Photocoupler output:

P2

Multi-Function Open

Factory setting is

48 VDC; 50 mA or less.

Collector Output 2

"

Speed Agree "

PC

Multi-Function Open

0 V

Collector Output common

R+

Receive input (+)

MODBUS

R–

Receive input (–)

communication

RS-485/422 MODBUS protocol,

S+

Send output (+)

RS-485 or RS-422.

19.2 kps max.

S–

Send output (–)

Table 1-3. Terminal Functions and Signals of Control Circuit

NOTES:

1.

These inputs have factory settings based on 2-wire reset. For 3-wire reset definitions, see Figure 1-6.

Continued