Yaskawa V7 Drives User Manual

Page 64

Advertising
background image

5-12

Continued

D.

Frequency Reference via Pulse Train Input

In order to set the Drive so the frequency reference comes from a pulse train, set the following
parameters.

Pulse Source Specifications

Low-level voltage: 0.8V or less

High-level voltage: 3.5 to 32V

Duty Cycle: 30 to 70% - high

Pulse Frequency: 0 to 30 kHz

n149 : Pulse Train Input Scaling

Factory Setting: 2500
Range: 100 to 3000 (x 10 Hz)

This parameter scales the incoming frequency on terminal RP by using the following equation

Frequency reference =

Pulse Source Frequency

*

n011

n149 * 10

E.

Frequency Reference via Serial Communications - See paragraph 5.14

FC

RP

GPD Drive

Pulse

Source

PARAMETER

SETTING

DESCRIPTION

n004

5

Sets reference source as a pulse train at terminals RP & FC

n149

User

Sets the input scaling for the pulse train input

Set

5.11 FREQUENCY REFERENCE SELECTION

Drive

Advertising
This manual is related to the following products: