Yaskawa V7 Drives User Manual

Page 116

Advertising
background image

6-6

Fault Display

Digital

RUN (Green)

Drive

Explanation

Causes and

Operator

ALARM (Red)

Status

Corrective Actions

EF

Check the external circuit

(External fault)

(sequence).

Drive receives an
external fault input from
control circuit terminal.
EF0: External fault

reference through
MODBUS
communications

EF1: External fault

input command from
control circuit
terminal S1

EF2: External fault input

command from control
circuit terminal S2

EF3: External fault input

command from control
circuit terminal S3

EF4: External fault input

Protective

command from control

Operation.

circuit terminal S4

Output is

EF5: External fault input

shut OFF

command from control

and motor

circuit terminal S5

coasts to

EF6: External fault input

a stop.

command from control
circuit terminal S6

EF7: External fault input

command from control
circuit terminal S7

CPF-00

Cycle power after checking

Drive cannot

the digital operator is

communicate with the digital

securely mounted.

operator for 5 sec. or

If the fault remains,

more when power is

replace the digital operator

turned ON.

or drive.

CPF-01

Cycle power after checking

Transmission fault

the digital operator is

occurred for 5 sec or more

securely mounted.

when transmission starts

If the fault remains,

with the digital operator.

replace the digital operator
or drive.

CPF-04

• Record all parameter

EEPROM fault of drive

data and initialize the

control circuit is detected.

constants. (Refer to
paragraph 5.__ for
constant initialization.)

• Cycle power.

If the fault remains,
replace the drive.

Table 6-2. Fault Displays and Corrective Actions - Continued