13 local/remote reference and sequence selection, Local/remote reference and sequence selection -14 – Yaskawa V7 Drives User Manual

Page 66

Advertising
background image

5-14

The Drive has the ability to have either a local or a remote reference and sequence selection.

Local -

Run and stop functions are controlled by the buttons on the digital operator (

n007). The

frequency reference can come from a digital preset reference (

n024 & n009) or the

digital operator pot (

n008).

Remote -

Run and stop functions are determined by parameter

n003. The frequency reference is

determined by parameter

n004.

Switching between local and remote is accomplished either by the LO/RE LED on the digital operator
or by the use of a multi-function input terminal programmed to data “

17” (see paragraph 5.18A).

n003 : Operation Method Selection

Factory setting:

1

n004 : Reference Selection

Factory setting:

2

n007 : Stop Key Function

Factory setting:

0

Range: 0 or 1

SETTING

DESCRIPTION

0

Run and stop is controlled by the

and

buttons on the digital operator.

Run and stop is controlled by the multi-function input terminals
2-Wire control - Run Forward (

n050 is set to a data of “1”)

Run Reverse (

n051 is set to a data of “2”)

1

3-Wire control - Parameter

n052 needs to be set to a data of “0

Run is controlled by a momentary closure on terminal S1
Stop is controlled by a momentary open on terminal S2
Forward/Reverse is controlled by terminal S3

2

Run and stop is controlled by serial communications

STOP

RESET

RUN

SETTING

DESCRIPTION

0

Frequency reference is controlled by the digital operator potentiometer.

1

Frequency reference is controlled by a digital preset speed (

n024) and is affected by n009.

2

Frequency reference is controlled by the analog input terminal

FR and is 0 - 10V DC

3

Frequency reference is controlled by the analog input terminals

FR and is 4 - 20mA

4

Frequency reference is controlled by the analog input terminal

FR and is 0 - 20mA

5

Frequency reference is controlled by the Pulse Train Reference terminal

RP.

6

Frequency reference is controlled by serial communications.

SETTING

DESCRIPTION

0

key is effective at all times (regardless of programming of

n003)

1

key is effective only when the run/stop command is from the digital operator (

n003 = 0)

STOP

RESET

STOP

RESET

5.13 LOCAL/REMOTE REFERENCE & SEQUENCE SELECTION