Yaskawa V7 Drives User Manual

Page 117

Advertising
background image

6-7

Fault Display

Digital

RUN (Green)

Drive

Explanation

Causes and

Operator

ALARM (Red)

Status

Corrective Actions

CPF-05

Cycle power.

A/D converter fault is

If the fault remains,

detected.

replace the drive.

CPF-06

Remove power to the

Option card connecting fault

drive.
Check the connection
of the digital operator.

CPF-07

Cycle power after checking

Operator control circuit

the digital operator is

(EEPROM or A/D

securely mounted.

converter) fault

If the fault remains,
replace the digital operator
or drive.

OPR (Operator

Cycle power.

connecting fault)

If the fault remains,
replace the drive.

CE (MODBUS

Check the communication

communications fault)

devices or communication
signals.

PF (Input Phase Loss)

Check input voltage.

Drive input power supply

Tighten terminal screws.

has an open phase or has

Check input voltage.

a large imbalance of voltage.

LF (Output Open Phase)

Check the wiring to the

An open phase occurred

motor.

at the Drive output.

Check motor for phase to
ground short.
Check motor impedance.

RH (Dynamic Braking

Resistor)

Table 6-2. Fault Displays and Corrective Actions - Continued

Protective
Operation.
Output is
shut OFF
and motor
coasts to a
stop.