Yaskawa V7 Drives User Manual

Page 41

Advertising
background image

2-5

DIGITAL OPERATOR

DESCRIPTION

KEY SEQUENCE

DISPLAY

Table 2-1. Open Loop Vector Startup Procedure - Continued

Set the motor “no load cur-
rent” in the drive.

Motor no load current is set
as a percentage of motor
rated current. It is calculated
using the formula:

I

noload

*100 = n110

I

rated

Where:
I

noload

= Motor no load current

(measured in the

previous step)

I

rated

= Motor rated current

(from motor
nameplate)

Example:
2.5 * 100 = 60

4.2

Press the

key four times.

DSPL

This completes the startup.
Make further programming
changes as required.

Press the

key to get out of the pro-

gramming mode.

DSPL

(1)

The number in the display may be different than shown.

(2)

Motor synchronous speed can be calculated using the following formula:

120 x motor rated frequency

synch. speed =

number of motor poles

For 60 Hz Rated Motors

Poles

Synchronous Speed

2

3600 RPM

4

1800 RPM

6

1200 RPM

8

900 RPM

PRGM

PRGM

PRGM

PRGM

FREF

Press the

key.

DATA
ENTER

Press the

key.

Use the

&

keys until the

number in the display matches calculated no-
load current.

V

V

DATA
ENTER

Press the

key four times.

V

(1)

(1)