n082 : Number of Auto-Restart Attempts

Factory setting:

0

Range: 0 - 10

When a fault occurs during operation, the Drive can be programmed for an auto-restart operation to
automatically reset the fault. Auto-restart operation will use the number of reset attempts set in this
parameter, up to the maximum of 10. When set to " 0 ", no auto-restarts will be attempted.

Fault contact will not actuate (change state) during auto-restart attempts.

• The following faults can be automatically reset:

oC:

Overcurrent

ou:

Overvoltage (OV)

• The number of restart attempts available will be reset to the

n082 setting when:

1. 10 minutes has elapsed without a fault occurring.
2. The RESET key, or external Fault Reset push button, is pressed.
3. Power is removed from the Drive.

n080

CARRIER FREQUENCY(kHz)

SLOPE

OUTPUT FREQUENCY(Hz)

MODE

SETTING

Maximum(Fc

MAX

)

Minimum(Fc

MIN

)

(=Fc)

Fo

F1

F2

1

2.5

2.5

0

NA

NA

CONSTANT

2

5.0

5.0

0

NA

NA

3

7.5

7.5

0

NA

NA

4

10.0

10.0

0

NA

NA

7

2.5

1.0

12

83.3

208.3

SYNCHRONOUS

8

2.5

1.0

24

41.6

104.1

9

2.5

1.0

36

27.7

69.4

n080 : Carrier Frequency

Factory Setting:

3

Range: 1 to 4; 7 to 9

The relationship between output frequency and carrier frequency is determined from the set value
of

n080 .

(a) For constant carrier frequency, set to " 1 ", " 2 ", " 3 ", " 4 ".

(b) For synchronous mode, set

n080 to " 7 ", " 8 ", or " 9 ". These setting values

establish carrier frequencies of 12f, 24f, or 36f, respectively.

Fc

MAX

CARRIER
FREQUENCY

SLOPE

Fc

MIN

0

F1

F2

OUTPUT FREQUENCY

5.5 CARRIER FREQUENCY

5.4 AUTO-RESTART