Yaskawa V7 Drives User Manual

Page 63

Advertising
background image

5-11

5.11 FREQUENCY REFERENCE SELECTION

Example 1 - Four preset references
Programming: n054 = 6 and n055 = 7

DIGITAL PRESET

S6

S5

Selectable Reference

(2)

Open

Open

n025

Open

Closed

n026

Closed

Open

n027

Closed

Closed

(2)

The Selectable Reference is chosen from the following

list:

C.

Jog Reference - See paragraph 5.12

REFERENCE SOURCE

PROGRAMMING

Digital Operator Speed Pot

n004 = 0

Digital Preset Reference parameter n024

n004 = 1

Analog Input Terminal FR

n004 = 2, 3, or 4

Pulse Train Reference

n004 = 5

Serial Communications

n004 = 6

Example 3 - Sixteen preset references
Programming: n053 = 6, n054 = 7, n055 = 8 and n056 = 9

Example 2 - Eight preset references
Programming: n054 = 6, n055 = 7 and n056 = 8

DIGITAL PRESET

S7

S6

S5

Selectable Reference

(2)

Open

Open

Open

n025

Open

Open

Closed

n026

Open

Closed

Open

n027

Open

Closed

Closed

n028

Closed

Open

Open

n029

Closed

Open

Closed

n030

Closed

Closed

Open

n031

Closed

Closed

Closed

DIGITAL PRESET

S7

S6

S5

S4

Selectable Reference

(2)

Open

Open

Open

Open

n025

Open

Open

Open

Closed

n026

Open

Open

Closed

Open

n027

Open

Open

Closed

Closed

n028

Open

Closed

Open

Open

n029

Open

Closed

Open

Closed

n030

Open

Closed

Closed

Open

n031

Open

Closed

Closed

Closed

n120

Closed

Open

Open

Open

n121

Closed

Open

Open

Closed

n122

Closed

Open

Closed

Open

n123

Closed

Open

Closed

Closed

n124

Closed

Closed

Open

Open

n125

Closed

Closed

Open

Closed

n126

Closed

Closed

Closed

Open

n127

Closed

Closed

Closed

Closed

Continued