• Magnetic contactor

Mount a surge protector on the coil. When using a magnetic contactor to start and stop the drive, do
not exceed one start per hour.

• Ground fault interrupter

Select a ground fault interrupter not affected by high frequencies. To prevent malfunctions, the
current should be 200mA or more and the operating time 0.1 second or more.

• AC and DC reactor

Install a reactor to connect to a power supply transformer of large capacity (600 kVA or more) or to
improve the power factor on the power supply side.

• Noise filter

Use a noise filter exclusively for the drive if radio noise generated from the drive causes other
control devices to malfunction.