n057 : Multi-function Output 1

Data

6 or 7 : Overtorque

(terminals MA, MB & MC)

Detection

n058 : Multi-function Output 2

(terminals P1 & PC)

n059 : Multi-function Output 3

(terminals P2 & PC)

A Form-C contact, or an open collector output, can be programmed to change states during an
overtorque detection condition.

EXAMPLE OF OVERTORQUE DETECTION

n096 setting:

2

— Overtorque enabled, only at set frequency, coast to stop

n057 setting:

6

— Output contact programmed for overtorque detection

n096 setting:

110 %

— Level at which overtorque is sensed

n099 setting:

1.0 s

— Time delay before overtorque event occurs

Detection level

(

n098 )

Detection

110%

time

OUTPUT

100%

(

n099)

CURRENT/

TORQUE

0

100%

Coast

MOTOR

stop

SPEED

0

RUN

SIGNAL

FAULT

SIGNAL

CONTACT

OUTPUT

(OVERTORQUE

DETECTION)

TERM. MA & MC)

Overtorque Detection Timing Diagram

5.20 OVERTORQUE DETECTION