TERMINAL

FUNCTION

VOLTAGE / SIGNAL LEVEL

L1 (R)

230V Drive: 200 / 208 / 220 / 230V at 50/60 Hz

L2 (S)

Main circuit input power supply

460V Drive: 380 / 400 / 440 / 460 / 480V

L3 (T)

at 50/60 Hz

T1 (U)

T2 (V)

Main circuit output

230V Drive: 0 - 200 / 208 / 220 / 230V

T3 (W)

460V Drive: 0 - 400 / 440 / 460 / 480V

B1

For connection of braking resistor (option)

B2

+1

DC Reactor terminals

+2

DC Bus terminals (+1 & –)

Ground terminal (100 ohms or less)

– – – –

Table 1-2. Main Circuit Terminal Functions and Voltages

Continued